Mechanical Structure

:

19" Rack

Dimensions

:

1800 X 600X400mm

Potentional

:

2 Amp.@24 Volts

Protection

:

IP 20

Environmental

:

As per QM 333 B2

Humidity

:

95 Percent 35'C


Programmable Parameters/Features
 

Main High cut-of

:

485 Volts

Main Low Cut-off

:

240 Volts

Mains High cut-in 

:

470 Volts

Mains Low cut-in 

:

265 Volts

Mains low cut-off 

:

250 Volts

DG High cut-off

:

250 Volts

DG Low cut-off  

:

195 Volts

Room Temp. cut-off

:

37'c(Programmable in 1degree step)

Room temp. cut-in

:

30' (Programmable in 1degree step)

DG overload limit  

:

Programmable up to 100  Amps)

DG short lock duration

:

Programmable up to 5 minutes)

DG long lock duration

 

Programmable up to 10minutes)

First start pulse duration

:

Programmable in steps of 1 sec (Factory default: -2 Seconds)                       

Second start pulse duration

:

Programmable in steps of 1 sec (Factory default: -3 seconds)                      

Third start pulse duration

:

Programmable in steps of 1 sec (Factory default: -4 seconds)                      

Stop pulse duration

 

programmable in steps of 1 sec (Factory default: -55 seconds)

Disable Emergency alarm 

:

Programmable

Disable Cylinder temp  

:

Programmable

 

 Alarms

Mains fail

DG ON

Load on DG

Overload

LLOP

Fuel low

Door open

Smoke

Room Temperature High

HCT

DG Stop fail

DG Start fail

Alternator fail

IPI Battery fail

Emergency